| CROSS-SECTIONAL AREA OF PHASE CONDUCTORS S | MINIMUM CROSS-SECTIONAL AREA OF THE CORRESPONDING PROTECTIVE CONDUCTOR (PE, PEN) SPA |
| S ≤ 16 | S |
| 16 < S ≤ 35 | 16 |
| 35 < S ≤ 400 | S/2 |
| 400 < S ≤ 800 | 200 |
| 800 < S | S/4 |
| a Current in the neutral may be influenced where there are significant harmonics in the load. | |
| Minimum terminal capacity for copper protective conductors (PE, PEN) | |
Source: IEC 61439-1 2011 Table 5