CROSS-SECTIONAL AREA OF PHASE CONDUCTORS S | MINIMUM CROSS-SECTIONAL AREA OF THE CORRESPONDING PROTECTIVE CONDUCTOR (PE, PEN) SPA |
S ≤ 16 | S |
16 < S ≤ 35 | 16 |
35 < S ≤ 400 | S/2 |
400 < S ≤ 800 | 200 |
800 < S | S/4 |
a Current in the neutral may be influenced where there are significant harmonics in the load. | |
Minimum terminal capacity for copper protective conductors (PE, PEN) |
Source: IEC 61439-1 2011 Table 5