Functional tests consist in checking the correct functioning
of all the circuits (electrical and electromechanical)
by simulating, as far as possible, the different service
conditions of the assembly.
For example, tests on current and voltage circuits can
be carried out by supplying the secondary circuits of
the CTs and VTs, without disconnecting the CTs from
the circuit.
Electrical checks may include the verification of the proper
operation of circuits and equipment, in particular:
- control, signaling, alarm, trip and reclosing circuits;
- lighting and heating circuits, if present;
- protection and measuring circuits (overcurrent, overvoltage,
earth, residual current trip units, contactors,
ammeters, voltmeters, etc.);
- terminals and contacts available in the terminal box;
- insulation control devices (also creepage distances
and clearances must be verified at level of connections
and adaptations carried out at workshop).
To carry out these checks, in addition to the normal mechanical
tools used for assembling, also some electrical
tools are necessary. A periodical calibration is necessary
to obtain reliable results.
The tools generally used are:
- a tester or multimeter;
- a test bench (AC and DC) to supply the assembly during
the test of the operation under voltage;
- a torque wrench (to check that the correct tightening
torques have been applied to the connections) and
other tools.
Nice work..!!
ReplyDelete