Visual inspections

They are carried out visually taking into account:

a) compliance of the assembly with diagrams, designations,

drawings and type of enclosures, number and

characteristics of equipment, cross-sectional area of

conductors and presence of identification marks on

cables and devices (initialing, inscriptions on plates,

etc.);

b) presence of components which allow the degree of

protection (roofs, seals) and the absence of faults on

the enclosure (cuts, perforations which might jeopardize

the degree of protection) to be guaranteed;

c) compliance with the specific prescriptions, if required

in the assembling list, such as:

- coating or treatment of busbars (resin coating, silver

plating, etc.);

- type of cable (fireproof, ecological, etc.);

- completion spare parts;

- painting check (color, thickness, etc.).