Saturday, September 14, 2013

Enclosure resistance to damp

This test, carried out in accordance with standard

ieC 60068-2-3, checks that the insulation characteristics

of the enclosure, busbars and conductor supports

are not affected after 4 hours' exposure in a steam

chest (40°C at 95% relative humidity).

the insulation used has a tracking current resistance

of at least 400 V, which means it is not very sensitive to

damp (group i and group ii according to ieC 60664-1).

0 comments: