Monday, December 30, 2013
Friday, December 13, 2013
Dead-front panels
Dead front is defined in Article 100 of the NEC as being “without live parts exposed to a person on the operating side of the equipment.” Section 408.38 requires that panel boards be mounted in cabinets, cutout boxes or enclosures designed for the purpose and shall be dead front. The term “dead front” is used in other places in the NEC, but basically, the NEC requires distribution panels, panel boards (load centers), switchboards (stage and theater) be constructed so that switches, circuit breakers and other electrical components can be operated without the user being exposed to live parts.
Tuesday, December 10, 2013
Circuit breaker accessories - Service releases
Shunt opening release
This allows circuit-breaker opening by
means of an electric command. Release
operation is guaranteed for a voltage
between 70% and 110% of the rated
power supply voltage Un, both in AC and
in DC. It is always fitted with an auxiliary
limit contact.
Under voltage release
This opens the circuit-breaker due to a
power supply failure to the release, or
voltage drops to minimum values of 0.7
x Un with a trip range from 0.7 to 0.35 x Un.
After tripping, the circuit-breaker can be
closed again, starting with a voltage
higher than 0.85 x Un. With the undervoltage
release de-energised, neither
circuit-breaker nor main contact closure
is possible.
Time-delayed undervoltage release
The undervoltage release can be combined
with an external electronic power
supply time-delay device, which allows
circuit-breaker opening to be delayed in
the case of a power cut to the release
itself, according to fixed time-delays of
0.5-1-2-3 [s], so as to avoid unwarranted
trips caused by temporary malfunctions.
It is available for the SACE S3, S4, S5,
S6, and S7 circuit-breakers with power
supply voltages at 110-220 V (50-60 Hz)
only coupled with an undervoltage release
at 310 V DC.
Shunt closing release
This allows circuit-breaker closure by
means of an electric command. Operation
of the release is guaranteed for a
voltage between 80% and 110% of the
rated power supply voltage Un, both in
AC and in DC.
ABB SASE
Information included in the design verification
The design verification serves to document compliance with the specifications
of this standard. It is comprised of 13 individual verifications.
For selected individual verifications, additional sub-verifications in subcategories
may be required. If selected verifications are not required
due to the application, the respective verification should, as a minimum
requirement, state that verification on the basis of the standard is not
required in this instance.
1. Strength of materials
Verification of material strength is divided into seven sub-points. If
an empty enclosure pursuant to IEC 62208 was used and no modifications
have been made which could influence the functioning
of the enclosure, no further strength testing of the materials for this
enclosure is required. Compliance with standard IEC 62208 should
then be confirmed in the design verification. However, verification
of the resistance of the insulating materials to abnormal heat and
fire for the components used in the busbar system and other insulating
materials should additionally be provided.
a. Resistance to corrosion
Resistance to corrosion can only be verified by testing. For resistance
to corrosion, the verification should stipulate the "testing"
method, the degree of severity and the test report number.
2. Properties of insulating materials – Thermal stability of
Enclosures
This evidence is only required for enclosures made from insulating
materials, or parts made from insulating materials mounted on the
outside of the enclosure, and which are relevant to the protection
category. Verification should state that the test was passed at a
temperature of 70 °C, for a duration of 168 h, and with a recovery
time of 96 h, and should also include the method and the test
report number/report number.
3. Properties of insulating materials – Resistance to abnormal
heat and fire due to internal electric effects
These properties should be verified using the "testing" method on
the material used, or using the "assessment" method with the data
sheets for the basic plastic material. Verification should state that
the properties of the insulating materials meet the requirements of
the glow-wire test depending on the three intended applications:
960 °C for parts necessary to retain current-carrying parts
in position
850 °C for enclosures intended for mounting in hollow walls
650 °C for all other parts
The design verification should include the test method, the result of
the test, and the test report or report number.
4. Resistance to ultra-violet (UV) radiation
Resistance to UV radiation only applies to enclosures and external
parts of switchgear and controlgear assemblies for outdoor installation.
Verification may be provided by testing or by assessing the
data from the original material manufacturer. The design verification
should include the test method, the result of the test method,
and the test report or report number.
5. Lifting
Verification for lifting can only be provided by testing. Verification
should state that the test was passed, indicating the maximum
number of sections that can be lifted and the maximum weight,
together with the test report number.
6. Mechanical impact
The impact resistance of a switchgear and controlgear assembly is
verified by testing. The design verification should state the method,
the tested IK protection category, and the corresponding test
report number.
7. Marking
There is no requirement to test markings made by moulding, pressing,
engraving or similar, as well as labels with a laminated plastic
surface. In such cases, it is sufficient to state the chosen technique
in the design verification. For all other types of marking, testing is
mandatory. The test outcome should be documented, stating the
test report number.
RITTAL (Standard compliant switchgear & controlgear production)
Tuesday, December 3, 2013
Calculation of the temperature rises in compliance with the Std. IEC 60890
Calculation of the powers generated by the different
components and dissipated inside the assembly
The calculation of the power losses reported in the
configurations shown is carried out by taking into account
the effective powers dissipated by the different
components.
Circuit-breakers
Given the power losses at the rated current (In) shown in
the following tables and the current which actually flows
through the circuit-breakers (Ib), it is possible to calculate
the effective power losses of the equipment:
The values thus obtained must be increasde by a factor
depending on the circuit-breaker type.
This coefficient is used to take into account the connections
which carry current to the circuit-breakers
Open-type and enclosed assemblies
According to the constructional typology the Standard
IEC 61439-1 distinguishes between open-type and enclosed
assemblies.
- Enclosed assembly
An assembly is enclosed when there are protected
panels on all its sides so as to provide a degree of
protection against direct contact not lower than IPXXB
(see Chapter 4). Assemblies intended to be installed
in common environments shall be of enclosed type
- Open-type assembly
An assembly, with or without front covering, in which
the live parts of the electrical equipment are accessible.
Such assemblies can be used only in places
where skilled persons have access for their use.
Monday, December 2, 2013
Rated electrical characteristics of an assembly
Rated voltage (Un)
Highest nominal value of the a.c. (r.m.s) or d.c. voltage,
declared by the assembly manufacturer, to which the
main circuit(s) of the assembly is (are) designed to be
connected. In three-phase circuits, it is the voltage
between phases.
Rated operational voltage (Ue)
it is the rated voltage of a circuit of an assembly which
combined with the rated current of this circuit determines
its application. For three-phase circuits such voltage corresponds
to the voltage between phases.
In an assembly there are usually a main circuit with its
own rated voltage and one or more auxiliary circuits with
their own rated voltages.
The manufacturer of the assembly shall state the limits of
voltage necessary for correct functioning of the circuits
inside the assembly.
Rated insulation voltage (Ui)
it is the voltage value of a circuit of an assembly to which test voltages
(power frequency withstand voltage) andthe creepage distances are referred.
The rated voltage of each circuit shall not exceed its
rated insulation voltage.
Rated impulse withstand voltage (Uimp)
it is the peak value of an impulse voltage which the circuit
of an assembly is capable of withstanding under specified
conditions and to which the values of clearances
are referred. It shall be equal to or higher than the values
of the transient overvoltages occurring in the system in
which the assembly is inserted.
Rated current of the assembly (InA)
It is a new characteristic introduced by the Std. IEC
61439 and normally indicates the maximum incoming
permanent and allowable load current or the maximum
current which an assembly is capable of withstanding.
The rated current shall be withstood in any case, provided
that the temperature-rise limits stated by the Standard
are complied with.
Rated current of a circuit (InC)
It is the current value to be carried out by a circuit without
the temperature-rise of the various parts of the assembly
exceeding the limits specified according to the testing
conditions of Clause 7.
Rated short-time current (Icw)
it is the r.m.s. value of the current for the short-circuit test
for 1 s time; such value, declared by the manufacturer
does not imply the opening of the protective device
and is the value which the assembly can carry without
damage under specified conditions, defined in terms of
current and time. Different Icw values can be assigned to
an assembly for different times (e.g. 0.2 s; 3 s). Manufacturer,
can withstand satisfactorily for the operating
time of the device under the specified test conditions.
Rated diversity factor (RDF)
it is the per unit value of the rated current, assigned by
the assembly manufacturer, to which outgoing circuits
of an assembly can be continuously and simultaneously
loaded taking into account the mutual thermal influences.
The rated diversity factor can be stated:
- for groups of circuits;
- for the whole assembly.
The rated diversity factor is:
The rated diversity factor multiplied by the rated current
of the circuits (In) shall be equal to or higher than the
assumed loading of the outgoing circuits (Ib).
The rated diversity factor is applicable to the outgoing
circuits of the assembly and demonstrates that multiple
functional units can be partially loaded.
When the manufacturer states a rated diversity factor,
this factor shall be used for the temperature-rise test,
otherwise reference shall be made to the values recommended
by the Standard 61439-1 in Annex E.
Rated frequency
value of frequency to which the operating conditions are
referred. If the circuits of an assembly are designed for
different values of frequency, the rated frequency of each
circuit shall be given.
-ABB technical application papers
Friday, November 29, 2013
IEC standards
IEC 60038 Standard voltages
IEC 60076-2 Power transformers - Temperature rise
IEC 60076-3 Power transformers - Insulation levels, dielectric tests and external clearances in air
IEC 60076-5 Power transformers - Ability to withstand short-circuit
IEC 60076-10 Power transformers - Determination of sound levels
IEC 60146 Semiconductor convertors - General requirements and line commutated convertors
IEC 60255 Electrical relays
IEC 60265-1 High-voltage switches - High-voltage switches for rated voltages above 1 kV and less than 52 kV
IEC 60269-1 Low-voltage fuses - General requirements
IEC 60269-2 Low-voltage fuses - Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications)
IEC 60282-1 High-voltage fuses - Current-limiting fuses
IEC 60287-1-1 Electric cables - Calculation of the current rating - Current rating equations (100% load factor) and calculation of losses - General
IEC 60364 Electrical installations of buildings
IEC 60364-1 Electrical installations of buildings - Fundamental principles
IEC 60364-4-41 Electrical installations of buildings - Protection for safety - Protection against electric shock
IEC 60364-4-42 Electrical installations of buildings - Protection for safety - Protection against thermal effects
IEC 60364-4-43 Electrical installations of buildings - Protection for safety - Protection against overcurrent
IEC 60364-4-44 Electrical installations of buildings - Protection for safety - Protection against electromagnetic and voltage disrurbance
IEC 60364-5-51 Electrical installations of buildings - Selection and erection of electrical equipment - Common rules
IEC 60364-5-52 Electrical installations of buildings - Selection and erection of electrical equipment - Wiring systems
IEC 60364-5-53 Electrical installations of buildings - Selection and erection of electrical equipment - Isolation, switching and control
IEC 60364-5-54 Electrical installations of buildings - Selection and erection of electrical equipment - Earthing arrangements
IEC 60364-5-55 Electrical installations of buildings - Selection and erection of electrical equipment - Other equipments
IEC 60364-6-61 Electrical installations of buildings - Verification and testing - Initial verification
IEC 60364-7-701 Electrical installations of buildings - Requirements for special installations or locations - Locations containing a bath tub or shower basin
IEC 60364-7-702 Electrical installations of buildings - Requirements for special installations or locations - Swimming pools and other basins
IEC 60364-7-703 Electrical installations of buildings - Requirements for special installations or locations - Locations containing sauna heaters
IEC 60364-7-704 Electrical installations of buildings - Requirements for special installations or locations - Construction and demolition site installations
IEC 60364-7-705 Electrical installations of buildings - Requirements for special installations or locations - Electrical installations of agricultural and horticultural premises
IEC 60364-7-706 Electrical installations of buildings - Requirements for special installations or locations - Restrictive conducting locations
IEC 60364-7-707 Electrical installations of buildings - Requirements for special installations or locations - Earthing requirements for the installation of data processing equipment
IEC 60364-7-708 Electrical installations of buildings - Requirements for special installations or locations - Electrical installations in caravan parks and caravans
IEC 60364-7-709 Electrical installations of buildings - Requirements for special installations or locations - Marinas and pleasure craft
IEC 60364-7-710 Electrical installations of buildings - Requirements for special installations or locations - Medical locations
IEC 60364-7-711 Electrical installations of buildings - Requirements for special installations or locations - Exhibitions, shows and stands
IEC 60364-7-712 Electrical installations of buildings - Requirements for special installations or locations - Solar photovoltaic (PV) power supply systems
IEC 60364-7-713 Electrical installations of buildings - Requirements for special installations or locations - Furniture
IEC 60364-7-714 Electrical installations of buildings - Requirements for special installations or locations - External lighting installations
IEC 60364-7-715 Electrical installations of buildings - Requirements for special installations or locations - Extra-low-voltage lighting installations
IEC 60364-7-717 Electrical installations of buildings - Requirements for special installations or locations - Mobile or transportable units
IEC 60364-7-740 Electrical installations of buildings - Requirements for special installations or locations - Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses
IEC 60427 High-voltage alternating current circuit-breakers
IEC 60439-1 Low-voltage switchgear and controlgear assemblies - Type-tested and partially type-tested assemblies
IEC 60439-2 Low-voltage switchgear and controlgear assemblies - Particular requirements for busbar trunking systems (busways)
IEC 60439-3 Low-voltage switchgear and controlgear assemblies - Particular requirements for low-voltage switchgear and controlgear assemblies intended to
be installed in places where unskilled persons have access for their use - Distribution boards
IEC 60439-4 Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies for construction sites (ACS)
IEC 60446 Basic and safety principles for man-machine interface, marking and identification - Identification of conductors by colours or numerals
IEC 60439-5 Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies intended to be installed outdoors in public places - Cable distribution cabinets (CDCs)
IEC 60479-1 Effects of current on human beings and livestock - General aspects
IEC 60479-2 Effects of current on human beings and livestock - Special aspects
IEC 60479-3 Effects of current on human beings and livestock - Effects of currents passing through the body of livestock IEC 60529 Degrees of protection provided by enclosures (IP code)
IEC 60644 Spécification for high-voltage fuse-links for motor circuit applications
IEC 60664 Insulation coordination for equipment within low-voltage systems
IEC 60715 Dimensions of low-voltage switchgear and controlgear. Standardized mounting on rails for mechanical support of electrical devices in switchgear and controlgear installations.
IEC 60724 Short-circuit temperature limits of electric cables with rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV)
IEC 60755 General requirements for residual current operated protective devices
IEC 60787 Application guide for the selection of fuse-links of high-voltage fuses for transformer circuit application
IEC 60831 Shunt power capacitors of the self-healing type for AC systems having a rated voltage up to and including 1000 V - General - Performance, testing and rating - Safety requirements - Guide for installation and operation
IEC 60947-1 Low-voltage switchgear and controlgear - General rules
IEC 60947-2 Low-voltage switchgear and controlgear - Circuit-breakers
IEC 60947-3 Low-voltage switchgear and controlgear - Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 60947-4-1 Low-voltage switchgear and controlgear - Contactors and motor-starters - Electromechanical contactors and motor-starters
IEC 60947-6-1 Low-voltage switchgear and controlgear - Multiple function equipment - Automatic transfer switching equipment
IEC 61000 Electromagnetic compatibility (EMC)
IEC 61140 Protection against electric shocks - common aspects for installation and equipment
IEC 61557-1 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures - General requirements
IEC 61557-8 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures
IEC 61557-9 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for insulation fault location in IT systems
IEC 61557-12 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures. Performance measuring and monitoring devices (PMD)
IEC 61558-2-6 Safety of power transformers, power supply units and similar - Particular requirements for safety isolating transformers for general use
IEC 62271-1 Common specifications for high-voltage switchgear and controlgear standards
IEC 62271-100 High-voltage switchgear and controlgear - High-voltage alternating-current circuit-breakers
IEC 62271-102 High-voltage switchgear and controlgear - Alternating current disconnectors and earthing switches
IEC 62271-105 High-voltage switchgear and controlgear - Alternating current switch-fuse combinations
IEC 62271-200 High-voltage switchgear and controlgear - Alternating current metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up toand including 52 kV
IEC 62271-202 High-voltage/low voltage prefabricated substations
Clearances & Creepage distances for LV panel boards
Clearances distances
Shortest distance in the air between two live conductors or between live
Conductors and exposed conductive parts.
14 mm for 12 kV impulse voltage
8 mm for 8 kV impulse voltage
5.5 mm for 6 kV impulse voltage
The IEC 60439-1 and IEC 61439-2 standards stipulate the minimum clearances
Required to withstand impulse voltage up to 2000 m above sea level.
Pollution degree 3.
Creepage distances
Shortest distance along an insulated material surface between two live
Conductors or between live conductors and exposed conductive parts.
16 mm for rated insulation voltage 1000 V AC and DC
12.5 mm for rated insulation voltage 750 V AC and DC
8 mm for rated insulation voltage 500 V AC and DC
See IEC 60439-1 and IEC 61439-2 table 16.
Pollution degree 3,
Material group 3a.
MILLIVOLT DROP TEST
The millivolt drop test is generally associated with
testing for weld quality on the armature. It is the
best test for verifying armature weld quality.
The millivolt drop test is the ultimate electrical test
for detecting bad welds. Unfortunately, it is
difficult to make on armatures with large diameter
wire and nearly impossible to make on armatures
with small wires.
The difficulty is breaking through the insulation on
the wire as it exits the tang or commutator bar
contact. The one testing contact, usually a sharp
knife edged probe, from the KOM (Kelvin Ohm
Meter) can cut through small wires and destroy
the armature. Contact with the knife-edge probe
needs to be made on each bar. Since this is such
a difficult test to perform, it is only practical as a
laboratory test.
Various test methods have been developed over
the last twenty years that come close to making
this test. These tests make it possible to test
100% of the armatures. However, none of these
tests are as accurate or repeatable as the Millivolt
Drop Test.
ESW's weld test, which uses techniques that have
been developed over the past 20 years, comes
very close to the Millivolt Drop Test. The
repeatability and speed of the test using a
stationary armature test fixture assures that a
reliable test has been performed.
Saturday, November 9, 2013
The new IEC 61439 standard
The new IEC 61439 standard applies to enclosures
for which the rated voltage is under 1000 V AC
(at frequencies not exceeding 1000 Hz) or 1500 V DC.
The standard defines the design verified ASSEMBLIES
and eliminates completely the categories TTA and PTTA.
In order to conform to the standard, type tests have been
replaced by a design verification which can be carried
out by the three following equivalent and alternative
methods: testing, calculation/measurement or
application of design rules.
The following parts are mentioned and do not have equal
weighting. There is a formal hierarchy. Each part cannot be
used individually:
−− IEC 61439-1 "General rules"
−− IEC 61439-2 "Power switchgear and control gear ASSEMBLIES"
−− IEC 61439-3 "Distribution boards"
−− IEC 61439-4 "ASSEMBLIES for construction sites"
−− IEC 61439-5 "ASSEMBLIES for power distribution"
−− IEC 61439-6 "Busbar trunking systems"
Part 1 is the general rules part and cannot be used alone to
specify an ASSEMBLY.
Part 2 defines the specific requirements of power switchgear
and controlgear ASSEMBLIES (PSC ASSEMBLIES) and must
be used with Part 1. This is the only part that has a double
role, it covers PSC ASS EMBLIES and any ASS EMBLY which
is not covered by any other specific parts.
Parts 3-X are still under preparation but are already mentioned
in Part 1. These could be more than four, as additional
parts may be developed as the need arises.
Summarising:
With the currently used IEC 60439, the rule
is "one part for each type of ASS EMBLY". With the new
IEC 61439 the rule is "two parts for each type of ASSEMBLY".
The compliance of an ASSEMBLY is declared referring
to the specific ASS EMBLY standard (e.g. IEC 61439-2),
and the compliance with the general rules (IEC 61439-1) is
always implicit. The sentence "TTA switchgear according to
IEC 60439-1" is now replaced by "Power switchgear and
controlgear
ASSEMBLIES according to IEC 61439-2, design
verified ASS EMBLY".
The validity of the two standards will overlap until 2014 and
prior to this date, ASSEMBLIES can be manufactured according
to IEC 61439 or IEC 60439.
Copyright by :
ABB The new standard for low-voltage
switchgear and controlgear assEmblies
IEC 60529 First Characteristic Numeral Degrees of Protection - Water
INDOOR
IP X1 Vertical Falling Drops 10 Min. Drip Test Limited Water Inside;
Not on Live Parts
IP X2 15° Vertical Falling Drops 10 min. 15° Drip Test Limited Water Inside;
Not on Live Parts
IP X3 Spraying Water 5 min. 120° Oscillating Tube or
5 min. Partial Spray
Limited Water Inside;
Not on Live Parts
IP X4 Splashing Water 10 min. 360° Oscillating Tube
or 5 Min. Full Spray
Limited Water Inside;
Not on Live Parts
IP X5 Waterjets Fire Hose 3.3 gal. (12.5L)/min Limited Water Inside;
Not on Live Parts
OUTDOOR
IP X6 Powerful Waterjets Fire Hose 26 gal. (100L)/Min. Limited Water Inside;
Not on Live Parts
IP X7 Temporary Submersion at Limited Depth Submerge 3 ft. (1m) – 30 Min. Limited Water Inside;
Not on Live Parts
IP X8 Prolonged Submersion at Limited Depth More Severe Than X7 Customer Agreement Limited Water Inside;
Not on Live Parts
IEC 60529 First Characteristic Numeral Degrees of Protection - Solids
>> IEC 60529 First Characteristic Numeral Degrees of Protection – Solids
Protection Test Method Pass Criteria
INDOOR
IP 1X Incidental Contact & Solid Objects Ø 50 mm – Probe No Penetration
IP 2X Incidental Contact & Solid Objects Ø 12.5 mm – Probe No Penetration
IP 3X Incidental Contact & Solid Objects Ø 2.5 mm – Probe No Penetration
IP 4X Incidental Contact & Solid Objects Ø 1.0 mm – Probe No Penetration
OD
IP 5X Dust Protected Circulating Dust Limited Dust Inside; Not on Live Parts
IP 6X Dust Tight Circulating Dust No Dust Inside
Thursday, October 24, 2013
Methods of explosion protection for electrical equipment
METHODS OF EXPLOSION PROTECTION
Method Type of Protection
Designed to prevent any means of ignition arising Ex e Increased Safety
Ex n or Ex N Non Sparking
Designed to limit the ignition energy of the circuit Ex I Intrinsic Safety
Designed to prevent the flammable mixture reaching Ex m Encapsulation
a means of ignition Ex p Pressurisation
Ex o Oil Immersion
Ex nR or Ex N Restricted Breathing
Designed to prevent any ignition from spreading Ex d Flameproof Enclosure
Ex q Powder Filling
Saturday, October 19, 2013
Minimum terminal capacity for copper protective conductors (PE, PEN)
CROSS-SECTIONAL AREA OF PHASE CONDUCTORS S | MINIMUM CROSS-SECTIONAL AREA OF THE CORRESPONDING PROTECTIVE CONDUCTOR (PE, PEN) SPA |
S ≤ 16 | S |
16 < S ≤ 35 | 16 |
35 < S ≤ 400 | S/2 |
400 < S ≤ 800 | 200 |
800 < S | S/4 |
a Current in the neutral may be influenced where there are significant harmonics in the load. | |
Minimum terminal capacity for copper protective conductors (PE, PEN) |
Source: IEC 61439-1 2011 Table 5
Saturday, October 12, 2013
Standard-compliant switchgear and controlgear production (Application of IEC 61439)
A new standard. A new opportunity. 3
Contents 4
One standard for all switchgear and controlgear assemblies 6
What has changed under the new standard? 8
What does the new standard mean for you? 10
Rittal – The System.
Complete solutions – Customised for IEC 61439 12
Strength of materials 14
Protection category of enclosures 16
Verification of protective circuit function 18
Insulating properties 20
Calculation of temperature rise 22
Tested busbar technology 24
The system for the standard 26
Preparation of the design verification 28
I. The design verification 29
II. Individual verifications and verification methods 31
III. Information included in the design verification 32
IV. Sample design verification 44
V. Verification of temperature rise using calculations 48
VI. Verification of short-circuit withstand strength 66
VII. Verification records of individual
switchgear and controlgear assemblies 70
VIII. The routine verification 73
IX. Complete verification of a switchgear and
controlgear assembly 78
X. Assembly cover sheet and design verification form 80
Copyright: c 2013 Rittal GmbH & Co. KG
DOWNLOAD :
http://www.rittal.com/belgium/downloads/brochures/eng/IEC61439_compliant_switchgear_controlgear_production.pdf
Guide to migration from IEC 60439 to IEC 61439 (XL3 Confugurable Assemblies IEC 60439 >>> IEC 61439)
This document only deals with distribution enclosures for advanced users (authorised persons), i.e. parts 1 and 2 of the new standard. Part 3 of standard IEC 61439 discusses DBO (Distribution Boards intended to be operated by Ordinary persons) only up to 250 A. One of the new features of this standard is that the table in appendix D (checking the design) covered laterin this document does not apply in 61439-3.
In addition in its new version, standard 61439-3 takes account of domestic normative references.
DOWNLOAD :
http://www.export.legrand.com/files/fck/pdf-EN/EXB12074_GUIDE_TABLEAUTIERS_EN.pdf