> Design verification
· Increased requirements for insulating materials and transient overvoltages withstand tests.
· Temperature rise verification:
ΓΌ Verification by test of each functional unit loaded alone with its rated current
ΓΌ Clear methods for the selection of representative samples of an Assembly system to be tested
ΓΌ Test done in 4 steps: individual functional units, main and distribution busbars, and complete
Assembly
ΓΌ Heating resistors only allowed to simulate circuits adjacent to a circuit under test
ΓΌ Possible verification by comparison with a tested design under strict conditions, including derating
ΓΌ Exemption of test (calculation) only allowed up to 1600 A instead of 3150 A under strict conditions,
including a 20% derating.
· Possible short-cricuit withstand verification by comparison with a tested design under strict
condition
· 200 operating cycles instead of 50 for locking, interlocking and withdrawable parts
· Lifting test (from IEC 62208)
· Corrosion resistance test for metallic parts (from IEC 62208).
> Routine verification
ΓΌ More detailed list of the verifications
ΓΌ More severe requirements for clearances
SCHNEIDER ELECTRIC