Friday, November 20, 2009

Type-tested (TTA) and Partially type-tested assemblies (PTTA)





Type-tested assemblies (TTA)

No.  
Requirement to be tested
TTA
1
Overtemperature limit
Proof of overtemperature limit by testing (type testing)
2
Insulation
Proof of insulation by testing
3
Short-circuit resistance
Proof of short-circuit resistance by testing (type testing)

4


Effectiveness of the PE conductor circuit

Proof of the perfect connection between bodies, switchgear assemblies and PE conductor circuits


Short-circuit resistance of the PE conductor circuit




Proof of the perfect connection between bodies of the switchgear assembly and PE conductor circuit (type testing)

Proof of the short-circuit resistance of the PE conductor by testing (type testing)

5
Creepage distances and clearances
Proof of creepage distance and clearances (type testing)
6
Mechanical function
Proof of mechanical function (type testing)
7
IP protection category
Proof of IP protection category (type testing)
8
Wiring, electrical function
Viewing of switchgear assemblies including wiring and electrical function testing if necessary (unit testing)
9
Insulation
Insulation testing (unit testing)
10
Protective measures
Checking of protective measures and continuous PE conductor circuits (unit testing)
11
Insulation resistance
Proof of insulation resistance if test was not carried out

Partially type-tested assemblies (PTTA)

No.
Requirement to be tested
PTTA
1
Overtemperature limit
Proof of compliance with overtemperature limit by testing or extrapolation
2
Insulation
Proof of insulation by testing or proof of insulation resistance
3
Short-circuit resistance
Proof of short-circuit resistance by testing or extrapolation of similar type-tested assemblies

4


Effectiveness of the PE conductor circuit

Proof of the perfect connection between bodies, switchgear assemblies and PE conductor circuits



Short-circuit resistance of the PE conductor circuit




Proof of the perfect connection between bodies of the switchgear assembly and PE conductor circuit


Proof of the short-circuit resistance of the PE conductor circuit by testing or respective design and arrangement of the PE conductor

5
Creepage distances and clearances
Proof of creepage distance and clearances
6
Mechanical function
Proof of mechanical function
7
IP protection category
Proof of IP protection category
8
Wiring, electrical function
Viewing of switchgear assemblies including wiring and electrical function testing if necessary
9
Insulation
Insulation test or proof of insulation resistance
10
Protective measures
Checking of protective measures
11
Insulation resistance
Proof of insulation resistance if test was not carried out