Tuesday, July 9, 2013

Sizing of protective earthing conductor

Below is based on IEC 60364-5-54. This table provides two methods of determining the appropriate c.s.a. for both PE or PEN conductors.

 

 

c.s.a. of phase
conductors Sph (mm2)

Minimum c.s.a. of
PE conductor (mm2)

Minimum c.s.a. of
PEN conductor (mm2)

Cu                       AI

Simplified
method (1)

Sph≤ 16

Sph(2)

Sph(3)

Sph(3)

16 < Sph ≤ 25

16

16

25 < Sph ≤ 35

25

35 < Sph ≤ 50

Sph/2

Sph/2

Sph > 50

Sph/2

Adiabatic method

Any size

    (3)  (4)

(1) Data valid if the prospective conductor is of the same material as the line conductor. Otherwise, a correction factor must be applied.
(2) When the PE conductor is separated from the circuit phase conductors, the following minimum values must be respected:

§  2.5 mm2 if the PE is mechanically protected

§  4 mm2 if the PE is not mechanically protected

(3) For mechanical reasons, a PEN conductor, shall have a cross-sectional area not less than 10 mm2 in copper or 16 mm2 in aluminium.
(4) Refer to table G53 for the application of this formula.

Wikipedia

Monday, July 8, 2013

Commercial and Industrial Power distribution systems

Power distribution systems used in multi-family, commercial, and industrial facilities are more complex. A power distribution system consists of metering devices to measure power consumption, main and branch disconnects, protective devices, switching devices to start and stop power flow, conductors, and transformers. Power may be distributed through various switchboards, transformers, and panel boards.

Good distribution systems don’t just happen. Careful engineering is required so that the distribution system safely and efficiently supplies adequate electric service to existing loads and has expansion capacity for possible future loads.

-          siemens

Saturday, July 6, 2013

Friday, July 5, 2013

Thursday, July 4, 2013

Busbars And Their Uses

Used in electrical power distribution, busbars are usually made out of aluminium or copper and they are able to conduct electricity to transmit power from the source of electric power to the load. They are usually supported by insulators and conduct electricity within switchboards, substations or other electric apparatus. Some typical applications of these devices can be to form the interconnectedness of the incoming and outgoing electrical transmission lines and transformers at an electrical substation; supplying huge amounts of amperes to the electrolytic process in an aluminium smelter by using large busbars and also interconnecting generators to the main transformers in a power plant.

 

The size of the busbar determines its application and the amount of current that it can carry safely. They can be tubular, solid or flat depending on the application and to serve different needs. A tubular busbar is hollow and this shape allows it to dissipate heat more efficiently as it has a high surface area. Hollow or flat shaped bus bars are prevalent in high current applications. Also, the hollow section of a busbar is generally stiffer as compared to a solid rod, thus this allows a greater span between busbar support in outdoor switchyards. The smallest cross-sectional area of a busbar can be as little as 10mm2, but electrical substations would make use of busbars with a diameter of more than 50 mm as they carry great amounts of amperes. Aluminium smelters would make use of these large busbars to carry tens of thousands of amperes to the electrochemical cells that produce aluminium from molten salts.

 

As they carry large amount of electricity, it is important to support the busbars with insulation to prevent any accidents from happening whereby someone may accidentally touch the bus bar. Insulation can either support the busbar or completely surround it. They can be prevented from accidental touch by placing the bus bars at an elevated height so it would not be easily accessible or by a metal earth enclosure. Some bus bars such as the earth bus bar can be bolted directly into the housing chassis of their enclosure. This prevents unwanted touch and also saves the bus bar from any damage it may incur when left exposed. There are several other ways that busbars can be connected to one another or the electrical apparatus with which they would be used with such as by bolting, clamping or welding connections. Switchgears, panelboards or busways usually contain the busbars and the electrical supply is split by the distribution boards into different circuits. Busways are a type of busbars that have a protective cover and are long in shape. Also referred to as bus ducts, these devices allow the electricity to branch out to different circuits at any point along its surface; unlike regular busbars that allow branching of the main supply only at one location.

 

The most common types of busbars present in the industry today are rigid busbars, strain busbars and insulated phase busbars. Each of these different types of busbars has different applications and uses. The rigid busbars are used in low, medium or high voltage applications, constructed with aluminium or copper bars and they make use of porcelain to insulate them. As for the strain busbars, they are mostly used in high voltage applications and are usually strung between the metal structures of a substation. They are held in place by suspension-type insulators. Lastly, as for the insulated-phase bus bars, they are used at medium voltage and similar to the rigid bus bars, they are rigid bars that are supported by insulators. These busbars are able to eliminate short circuits between adjacent phases.

 

Monday, July 1, 2013

Enclosure Design for EMC

Most equipment manufactures choose to design custom housings for their electronics products

in order to differentiate them in the market place. Usually enclosure design is driven by the two

beasts of beauty and cost, with EMC requirements an irritating afterthought.

The ideal enclosure from an EMC point of view is the perfect Faraday cage. Take the PCBs

that make up a typical product, wrap them in a seamless monolith of copper without apertures

and bingo! You’ve fixed it. Unfortunately this solution is impractical.

The art of good enclosure design is therefore to get “as close as is necessary” to the Faraday

cage, without sacrificing the aesthetic appeal of the product or significantly increasing its cost.

For most designers “As close as is necessary” is usually defined as meeting standard or type

specific requirements. This usually involves at least:

 

(i) Containing Radiated Emissions

(ii) Providing Radiated Immunity

(iii) Providing ESD Immunity

(iv) Providing Fast Transient Immunity

In designing a compliant enclosure the designer needs to look at the following:

(i) Mechanical components - their material composition and coatings

(ii) Electrically bonding the enclosure components

(iii) Electrically bonding the internal hardware and its interfaces to the enclosure

(iv) Dealing with apertures in the enclosure

(v) Screening and partitioning inside the enclosure

(vi) Earthing the product

 

Component Material and Coatings

 

Generally the enclosure designer will work with components made from folded steel or

aluminium alloy or bulk extruded alloy and possibly vacuum formed aluminium or plastic.

Where the volumes of finished product justify the tooling expense, the designer might also use

injection moulded plastic or rubber or die cast aluminium.

Often housings made entirely of conductive metal components form poor EMC

enclosures simply because the individual components have been painted or coated in a

non-conductive material.

There are however a wide range of affordable conductive coatings available. For example:

= For aluminium components - alochrome plating rather than non-conductive anodising.

= For steel components - zinc galvanising or passivated zinc plating (zinc and chromate

passivated) for corrosion resistance. Where aesthetic appeal is important - bright nickel

or chromium plating. Note: Zintec is a sheet steel with conductive zinc coating and can

be used as an alternative to plating where corrosion at the cut edges of a component is

not an issue.

= For plastic components - internal metalisation or conductive carbon coating. Partially

conductive carbon loaded plastics can be used but often the strength and flexibility of a

loaded plastic is inferior to an unloaded component.

Friday, June 28, 2013

Saturday, June 22, 2013

NEMA Ratings and IP Equivalency Chart

NEMA Rating

IP Equivalent

NEMA Definition

IP Definition

 

1

IP10

Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt

1 = Protected against solid foreign objects of 50mm in diameter and greater

0 = Not Protected

2

IP11

Enclosures constructed for indoor used to provide a degree of protection to personnel against incidental contact with the enclosed equipment, to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids

1 = Protected against solid foreign objects of 50mm in diameter and greater

1 = Protected against vertically falling water drops

3

IP54

Enclosures constructed for either indoor or outdoor used to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to proved a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and that will undamaged by external formation of ice on the enclosure

5 = Protected against dust - Limited to ingress (no harmful deposit)

4 = Protected against water sprayed from all directions - Limited to ingress permitted.

3R

IP14

Enclosures constructed for either indoor or outdoor used to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, and snow; and that will be undamaged by external formation of ice on the enclosure

1 = Protected against vertically falling water drops

4 = Protected against water sprayed from all directions - Limited to ingress permitted.

3S

IP54

Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and in which the external mechanism(s) remain operable when ice laden.

5 = Protected against dust - Limited to ingress (no harmful deposit)

4 = Protected against water sprayed from all directions - Limited to ingress permitted.

4

IP66

Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water; and that will be undamaged by the external formation of ice on the enclosure

5 = Protected against dust - Limited to ingress (no harmful deposit)

6 = Protected against strong jets of water from all directions - Limited to ingress permitted.

4X

IP66

Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and corrosion; and that will be undamaged by thee external formation of ice on the enclosure

5 = Protected against dust - Limited to ingress (no harmful deposit)

6 = Protected against strong jets of water from all directions - Limited to ingress permitted.

5

IP52

Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against settling airborne dust, lint, fibers, and flyings; and to provide a degree of protection against dripping and light splashing of liquids.

5 = Protected against dust - Limited to ingress (no harmful deposit)

2 = Protected against direct sprays of water up to 15° from the vertical.

6

IP67

Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during occasional temporary submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure.

6 = Totally protected against dust

7 = Protected against the effects of temporary immersion between 15cm and 1m. Duration of test 30 minutes.

6P

IP67

Enclosures constructed for either indoor or outdoor use to provide a degree of protection to the personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during prolonged submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure

6 = Totally protected against dust

7 = Protected against the effects of temporary immersion between 15cm and 1m. Duration of test 30 minutes.

12 and 12K

IP52

Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flying; and against dripping and light splashing of liquids

5 = Protected against dust - Limited to ingress (no harmful deposit)

2 = Protected against direct sprays of water up to 15° from the vertical.

13

IP54

Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against the spraying, splashing, and seepage of water, oil, and noncorrosive coolants.

5 = Protected against dust - Limited to ingress (no harmful deposit)

4 = Protected against water sprayed from all directions - Limited to ingress permitted.

 

IP Codes in accordance with IEC 529 & UL

There are several different uses of IP Codes, as described in IEC 529. IP Codes can have the following arrangement:

·         First character only, such as IP 3X

·         Second character only, such as IP X4

·         Both characters, such as IP 34

The first character indicates the degree of protection against the ingress of solid foreign objects. First character definitions are as follows:

0 - Non-protected

1 - Protected against solid foreign objects of 50 mm diameter and greater

2 - Protected against solid foreign objects of 12.5 mm diameter and greater

3 - Protected against solid foreign objects of 2.5 mm diameter and greater

4 - Protected against solid foreign objects of 1.0 mm diameter and greater

5 - Dust-protected

6 - Dust-tight

The second character of the IP Code indicates the degree of protection against the ingress of water with harmful effects. Second-character definitions are as follows:

0 - Non-protected

1 - Protected against vertically falling water drops

2 - Protected against vertically falling water drops as the enclosure is tilted 15 degrees

3 - Protected against spraying water

4 - Protected against splashing water

5 - Protected against water jetting

6 - Protected against powerful water jetting

7 - Protected against temporary immersion

8 - Protected against continuous immersion

UL sample requirements

Some UL testing chambers are limited in size. Please note that these size restrictions apply only for the tests specified below. If your sample will not fit into the test chambers, a smaller prototype may be used as long as the same type of hinges, gaskets, and other mechanisms are used at the same pressures.

·         IP 5X/6X -- Sample must fit into dust chamber measuring 3-1/2 ft. wide by 3 ft. tall by 7 ft. long. The door to the chamber measures 2 ft. by 3-1/2 ft.

·         IP X7/X8 -- Sample must fit into container measuring 23 in. diameter by 6 ft. deep.

 

UL 508 - The UL Safety Standard for Industrial Control Equipment

Industrial Control Equipment is a term commonly used to represent discrete components ranging from selector switches, relays, contactors, motor starters, timers, pilot lights, to complex system of these components. It encompasses more than 30 different product categories and 100 different devices (See Figure1).

 

Figure 1: Examples of industrial control devices covered by UL 508

Industrial Control Devices

Examples

Motor starters and controllers

Including manual, magnetic, and solid-state starters and controllers

Overload relays

Including thermal, magnetic, and solid-state overload relays

Control circuit switches and relays

Including pushbutton stations, selector switches, time-delay relays and pilot lights

Switches

Including float, flow, pressure, vacuum-operated, mercury-tube and proximity switches

Autotransformers, resistors and rheostats

Variable voltage and motor starting

Programmable controllers

Including numerical control systems and industrial microprocessor/computer systems

 

Industrial Control Equipment is used extensively in industrial applications including starting, stopping, regulating, controlling, reversing, changing speed, or protecting electric motors. Components for motor control are installed primarily in control panels, motor control centers, industrial machines as well as energy distribution assemblies.

Industrial Control Equipment is required to be designed, built and evaluated for their function and safety in compliance with an established National / International standard. UL 508, covers the safety requirements for Industrial Control Equipment.